			Ampco are manufacturers of a wide range of hazardous area generators to IECEx and ATEX standards.
			Manufacturers of Generators for Hazardous Environments
		 
		
			OFFSHORE GENERATOR EQUIPMENT FOR OIL AND GAS INDUSTRY, ZONE 2 HAZARDOUS AREA - 200KVA 
			 
			
				- ZONE 2 HAZARDOUS AREA COMPLIANT
- PRODUCES 200KVA, 480 VAC, 3 PHASE + NEUTRAL, 60HZ
- OTHER POWER OUTPUTS AVAILABLE 

			
				Operation/Service
				Zone 2 Diesel driven generator set mounted in a DNV 2.7-1 certified enclosure producing 200kVA @ 0.8pf, 480VAC, 3 phase + neutral, 60Hz output.
				For use in oil, gas and petrochemical industry.
					
				
				Components
				Caterpillar C9 engine rated at 361BHP @ 1800 RPM fitted with an AMPCO Zone 2 generator with electronic control and safety shutdown system, consisting of:
				
				
					-  Engine over-speed 
					
- Coolant temperature trip 
- Oil pressure trip
- Gas detection trip
					
- Exhaust temperature trip
- Trickle charger for unit batteries
- Battery powered engine start
					
- Electrical output monitoring system
- Electrical isolator switch
- Electrical output connection panel 
 
			
				Control Panels
				The engine control panels accommodate all engine and generator controls and indicators. This includes: 
				
					- MCCB 
- Over/under voltage protection
- Over/under frequency protection
- Meters – voltage, Hz, amps
- Start and Stop Switch
- Emergency Stop
- Engine Speed
- Engine oil pressure trip light 
- Engine exhaust temperature trip light
- Engine coolant temperature trip light
- Engine data display
Fuel Tank
	- 1500L Fuel tank capacity 
- During periods of 100% operation this fuel tank capacity allows for a run time of 22 hours 
Safety/Environmental 
	- Bunding for containment of fluids should there be any leaks or spills 
- Drain Points 
- Guarding supplied around all moving parts 
 
			
				Standards/Certification
				IECEx
				2014/34/EU ATEX Equipment Directive
				2006/42/EC Machinery Directive 
				DNV 2.7-1 Container IEE Wiring Regulations
				2000/14/EC Noise emission in the environment by equipment for use outdoors as amended by 2005/88/EC 
				Mass 
				Maximum Gross:		16,000kg Actual Weight:		13,400kg Frame Tare Weight:	  2,600kg 
				Dimensions (LxWxH)
				 LENGTH: 5,172	mm
				WIDTH:                        2,438	mm
				HEIGHT:                       3,148	mm
				Design/ambient Temperature
				 Minimum:	-20˚C 
				Maximum:	+45˚C 
			 
			Zone 2 Generator Instrumentation and Control Panels
			